Air-to-Water Heat Pump 4.3-18.7 kW 80°C A+++ at 55°C, Operation to -30°C – ECU149-SBY
The ECO-TEC ECU149-SBY is a high-temperature R290 air-to-water heat pump with a published heating capacity of 4.3–18.7 kW at the stated A7/W35 conditions. Its product specifications specifies supply-water temperatures up to 80°C and an outdoor operating range down to -30°C. These are operating-envelope statements, not guarantees of identical thermal output at every temperature.
Features and operation
Inverter-controlled operation enables the unit to modulate output according to the building load. This can reduce unnecessary cycling where the actual load is below maximum output. Existing radiator systems can benefit from the high supply-temperature capability, but the required flow temperature, flow rate and heat loss of the building must be assessed separately before replacing a boiler.
The published energy-class claim is A+++ at 55°C. Energy labels are tied to specific assessment conditions; this statement alone is not a model-specific, independently verified SCOP value. The table distinguishes heating at A7/W35 and A7/W55 and cooling at A35/W18 and A35/W7, including rated or modulating capacity and power input where provided.
Planning and selection
The unit uses R290 refrigerant, inverter/EVI technology and Wi-Fi monitoring. The original information indicates a three-year warranty. Installation must follow the appropriate R290 safety requirements and the product instructions. Electrical supply, circulation pump, water flow, pressure drop and dimensions are listed below for equipment selection.
Use the exact test-point and hydraulic data from this table when designing the installation. Nominal heating output, maximum output, annual efficiency and electrical power draw describe different quantities and must not be substituted for one another.
Technical specifications
The table retains model values and units from the original product listing. Values apply at the specified test conditions.
| Parameter | Conditions | Value |
|---|---|---|
| Electrical supply | – | 400V / 3N~ / 50Hz |
| Refrigerant | – | R290 |
| Refrigerant charge | – | 1.2 kg |
| Outdoor operating temperature | – | -30°C ~ +43°C |
| Heating capacity | A7/W35 | 4.3 – 18.7 kW |
| Rated heating capacity | A7/W35 | 12 kW |
| Heating power input | A7/W35 | 0.7 – 4.5 kW |
| Heating capacity | A7/W55 | 4.3 – 18.2 kW |
| Rated heating capacity | A7/W55 | 12 kW |
| Heating power input | A7/W55 | 0.9 – 6.2 kW |
| Cooling capacity | A35/W18 | 3.8 – 15.5 kW |
| Cooling power input | A35/W18 | 0.8 – 5.5 kW |
| Cooling capacity | A35/W7 | 2.8 – 12.8 kW |
| Cooling power input | A35/W7 | 1.2 – 5.4 kW |
| Maximum power input | – | 8.0 kW |
| Maximum current | – | 12 A |
| Sound pressure level | – | 40 dB(A) |
| Sound power level | – | 55 dB |
| Net weight | – | 214 kg |
| Unit dimensions (L × W × H) | – | 1438 x 545 x 1105 mm |
| Transport dimensions | – | 1588 x 623 x 1206 mm |
| Circulation pump | – | Included |
| Water flow rate | – | 2.06 / 1.3 m³/h |
| Water connection | – | 1 inch |
| Pressure drop | – | 20 kPa |
| Pump head | – | 7.5 m |
| Fan type | – | DC Motor |
| Number of fans | – | 1 |
For specification and commissioning, consult the current product datasheet and installation instructions. Seasonal SCOP is not derived or published from isolated COP values.