Product overview
Industrial Heat Pump 50 kW R290 High Temperature – ECPL500
The ECO-TEC ECPL500-SBY industrial R290 heat pump has a published heating capacity of 13.63–50.00 kW. It is intended for heating, cooling and hot-water applications that require a high-output air-to-water unit. The product description states a possible water temperature of up to 70°C, subject to the operating conditions and system design.
Features and operation
This model uses R290 refrigerant, inverter technology and integrated Wi-Fi monitoring. Variable output allows the machine to respond to changes in thermal demand; the unit must nonetheless be selected from its capacity and power-input data at the intended air and water temperatures. The listed outdoor operating limit reaches -25°C. Performance at that limit must not be inferred from nominal values alone.
The technical table contains separate heating, cooling and domestic-hot-water operating conditions, with heating and electricity-input ranges as well as a COP range. These parameters are not interchangeable: the published COP range is not a certified seasonal SCOP. The technical specification also identifies the compressor count, fan, hydraulic connection, water flow and shipping dimensions.
Planning and selection
For an industrial installation, check the required heating-water supply temperature, minimum circulating flow, electrical supply, system controls and commissioning conditions. R290 installation and service requirements must be considered by qualified personnel. The description mentions a three-year warranty and energy classes up to A+++ for the range; confirm the applicable documentation for this exact equipment.
Testing conditions A, B, C and D are referred to in the original technical description. They should accompany any interpretation of the output and input figures; do not treat a single published COP or electrical-input figure as an annual consumption estimate.
Technical specifications
The table retains model values and units from the original product listing. Values apply at the specified test conditions.
| Model | ECPL500-SBY |
|---|---|
| Heating capacity (A) | 13.63~50.00 kW |
| Heating power input (A) | 4.36~16.00 kW |
| COP range (A) | 3.12–4.62 |
| Cooling capacity (B) | 9.27~34.00 kW |
| Cooling power input (B) | 3.91~14.35 kW |
| Hot-water heating capacity (C) | 16.36~70.00 kW |
| Hot-water power input (C) | 5.29~19.40 kW |
| Hot-water heating capacity (D) | 19.4 kW |
| Hot-water power input (D) | 8.24~28.77 kW |
| Rated power input | 6.01~22.00 kW |
| Rated current | 30.0 A |
| Electrical supply | 380~415V/3N~/50Hz |
| Number of compressors | 2 |
| Compressor type | Rotary |
| Number of fans | 1 |
| Fan power | 750 W |
| Fan rotational speed | 850 RPM |
| Refrigerant | R290 / 1.5 kg x 2 |
| Noise level | 52.6 dB(A) |
| Hydraulic connection | 1.5 inch |
| Water flow rate | 5.33 m³/h |
| Net unit dimensions (L/W/H) | 1195 / 980 / 1921 mm |
| Net weight | 363 kg |
| Shipping weight | 423 kg |
For specification and commissioning, consult the current product datasheet and installation instructions. Seasonal SCOP is not derived or published from isolated COP values.