Product overview
High-Temperature Heat Pump 8.9 kW R290
The ECO-TEC ECP089-SBV is an R290 air-to-water heat pump for space heating, optional cooling and domestic hot water preparation. The published heating-capacity range is 3.10–8.90 kW. The published product information describes high-temperature operation, with a stated maximum supply-water temperature of 75°C, which may be useful where conventional radiators require warmer water.
Features and operation
The inverter control adjusts compressor output to the actual thermal demand. Remote access through the integrated Wi-Fi module allows operating settings and status to be monitored from a compatible device. The product information also mentions enhanced compressor control for low outdoor temperatures, with an advertised operating capability down to -25°C; delivered heating capacity at that point must be checked against the relevant performance data.
R290 is the refrigerant identified for this product. Equipment installation and servicing must take account of the refrigerant properties and the manufacturer’s instructions. The selection of the outdoor unit and the hydraulic accessories depends on the application, including the space-heating circuit, hot-water preparation, frost protection and required electrical power.
Planning and selection
The product description specifies a three-year warranty and energy classes up to A+++ for the range. These statements are reproduced as product-description information; any specific energy-label rating and warranty conditions should be checked for the selected model. COP is a point-in-time efficiency ratio under specified conditions, not the same as seasonal performance SCOP.
Below, the full technical table from the original product is presented with translated labels. Where one table compares several ECO-TEC models, use the column for ECP089-SBV when choosing equipment. Verify minimum water flow, supply voltage, sound data and heating output at the design conditions before ordering.
Technical specifications
The table retains model values and units from the original product listing. Values apply at the specified test conditions.
| Model | ECP089-SBV | ECP149-SBY | ECP220-SBY |
|---|---|---|---|
| Heating capacity (kW) | 3,10 ~ 8,90 | 5,40 ~ 14,95 | 8,00 ~ 22,00 |
| Heating power input (kW) | 0,65 ~ 2,10 | 1,05 ~ 3,85 | 1,60 ~ 6,90 |
| COP (coefficient of performance) | 4,08 | 3,88 | 4,44 |
| Refrigerant / charge | R290 / 0,5 kg | R290 / 0,85 kg | R290 / 1,3 kg |
| Cooling capacity (kW) | 1,20 ~ 5,72 | 3,60 ~ 10,50 | 4,20 ~ 15,00 |
| Cooling power input (kW) | 0,65 ~ 2,40 | 1,12 ~ 4,47 | 1,80 ~ 7,30 |
| DHW capacity (kW) | 3,92 ~ 10,68 | 6,50 ~ 18,50 | 10,00 ~ 27,00 |
| DHW power input (kW) | 0,78 ~ 2,47 | 1,27 ~ 4,65 | 1,90 ~ 7,10 |
| Maximum power input (kW) | 3,0 | 5,30 | 8,3 |
| Maximum current (A) | 13,5 | 10,5 | 15,0 |
| Power supply | 220-240V~/50Hz | 380~415V/3N~/50Hz | 380~415V/3N~/50Hz |
| Number of compressors | 1 | 1 | 1 |
| Compressor type | Rotary | Rotary | Rotary |
| Number of fans | 1 | 1 | 2 |
| Fan power input (W) | 150 | 170 | 75 |
| Fan speed (rpm) | 600 | 600 | 600 |
| Circulation pump power input (W) | 60 | 60 | 160 |
| Noise level (dB(A)) | 38 ~ 52 | 39 ~ 52 | 42 ~ 54 |
| Water connection (inch) | 1 | 1 | 1 |
| Water flow (m³/h) | 1,0 | 1,7 | 2,9 |
| Internal pressure drop (kPa) | 20 | 30 | 45 |
| Pump head (m) | 7,5 | 5,5 | 10,2 |
| Dimensions mm (L/W/H) | 1167/420/790 | 1287/500/928 | 1247/540/1329 |
| Net weight (kg) | 80 | 160 | 202 |
For specification and commissioning, consult the current product datasheet and installation instructions. Seasonal SCOP is not derived or published from isolated COP values.